Products |
 |
|
|
|
|
|
|
|
 |
|
 |
|
Low Smoke Non-halogen Flame-retardant Cable |
|
 |
|
|
|
|
|
|
Low
Smoke Non-halogen Flame-retardant Cable
(UL Listed E202443)
Type and designation
Type
|
designation
|
RHH
|
Low
smoke, non-halogen and flame-retardant cable
|
Description of the purpose
The insulation material
of the cable is non-halogen cross-linked Polyolefin
compound. It is good flame-retardant and fire resistant.
When a fire occurs, the cable prevents fire spreading.
Even if the cable were ignited, it would not emit
toxic halogenous gas. It's safer, more reliable
and less harmful to environment than PVC insulated
cables. The cable is widely used in high rises,
subway, nuclear power station and large public buildings.
|
 |
Standard
UL 44
|
Specification
and Construction (mm) |
Nominal cross sectional
area (AWG)
|
Conductor structure
Number/diameter
of single wire
|
Insulation thickness
|
Maximum outer diameter
|
14
|
41/0.254
|
1.14
|
4.20
|
12
|
65/0.254
|
1.14
|
4.75
|
10
|
104/0.254
|
1.14
|
5.36
|
8
|
7/1.23
|
1.52
|
6.77
|
6
|
7/1.56
|
1.52
|
7.96
|
4
|
7/1.96
|
1.52
|
9.34
|
2
|
7/2.47
|
1.52
|
10.50
|
1/0
|
19/1.89
|
2.04
|
13.76
|
2/0
|
19/2.12
|
2.04
|
14.68
|
3/0
|
19/2.39
|
2.04
|
16.03
|
4/0
|
19/2.68
|
2.04
|
17.56
|
350Kcmil
|
37/2.47
|
2.41
|
22.44
|
750Kcmil
|
61/2.82
|
2.80
|
30.51
|
Note: Any specification can be produced in accordance
with the purchasers' requirement.
Main
technical performance
Test Item
|
Test Requirement
|
Test Result
|
Test Standard
|
Oxygen index
|
>28%
|
48%
|
ASTM
D 2863
|
Cold bend test
|
Pass
|
Pass
|
UL
1581
|
Smoke density
|
Pass
|
Pass
|
ASTM
E 662
|
Vertical flame test
|
Pass
|
Pass
|
UL 1581
|
|
|
|
|
|
|
|
|
|