Products |
 |
|
|
|
|
|
|
|
 |
|
 |
|
PVC Insulated Nylon Sheathed Cable |
|
 |
|
|
|
|
|
|
PVC
Insulated Nylon Sheathed Cable
(UL Listed E210924,E246599)
Type and temperature rating
TYPE
|
THHN
|
THWN
|
THWN-2
|
TFN
|
TFFN
|
Temperature rating
|
90℃ Dry
|
75℃ Dry or Wet
|
90℃ Dry or Wet
|
90℃Dry or Wet
|
90℃Dry or Wet
|
Description of the purpose and usage properties
The nylon sheathed cable
has more excellences in physical and electrical
performance than the PVC cable.
The cable has smaller outer diameter, lighter weight,
less static friction coefficient than the same size
of PVC cable, which greatly improve safety and convenience
in installation and assembly of the cable.
It is self-lubrication, and has good resistance
to corrosion, oil, acids, alkali, and moisture.
The cable is widely used in fixed installation,
home appliance, lighting equipment, construction
and aviation engine room with voltage up to 450/750V.
Its permitted long term working temperature shall
be 70℃ or 90℃, installation temperature shall be
over 0℃, and maximum bending radius shall be not
less than 4 times of outer diameter of the cable.
|
 |
Standard
UL62 UL83
|
Specification and construction (mm)
|
Normal
wire size(AWG) |
Insulation thickness |
Nylon sheath thickness |
Normal wire
size (AWG) |
Insulation thickness |
Nylon sheath thickness |
18 |
0.38 |
0.10 |
9-5 |
0.76 |
0.13 |
16 |
0.38 |
0.10 |
4-2 |
1.02 |
0.15 |
14 |
0.38 |
0.10 |
1-4/0 |
1.27 |
0.18 |
12 |
0.38 |
0.10 |
213-500kcmil |
1.52 |
0.20 |
11-10 |
0.51 |
0.10 |
501-1000kcmil |
1.78 |
0.23 |
Main technical performance
Test Item
|
Test Requirement
|
Test Result
|
Test Standard
|
Flame test
|
Pass
|
Pass
|
UL 1581
|
Insulation resistance
in water
|
Pass
|
Pass
|
UL
1581
|
Convolute and cold bend
test
|
No cracks
|
No cracks
|
UL 1581
|
Oil resistance test
|
Pass
|
Pass
|
UL 1581
|
Delivery
The cable shall be delivered in coil. Each package
of delivery shall be 100 meters, among which can
include the short wires of no less than 10 meters,
and the length of the short wires shall not be over
10% of total length of each package.
Any delivery length shall be permitted in accordance
with the purchasers' requirement
|
|
|
|
|
|
|
|
|