Products |
|
|
|
|
|
|
|
|
|
|
|
|
American Standard PVC Insulated Cable |
|
|
|
|
|
|
|
|
American
Standard PVC Insulated
Cable
(UL Listed E210924)
Type, temperature rating and voltage rating
Type |
TW |
THW |
THW-2 |
TFF |
Temperature
rating |
60℃ |
75℃ |
90℃ |
60℃ |
Voltage
rating |
600V |
600V |
600V |
600V |
Description
of the purpose
The cable is
primarily used in building wiring.
|
|
Standard
UL62 UL83
|
Specification
and construction (mm) |
Nominal cross sectional
area (AWG) |
Conductor structure
Number/diameter
of single wire |
Insulation thickness |
Maximum outer diameter |
1 |
208/0.511 |
2.03 |
13.43 |
2 |
168/0.511 |
1.52 |
11.76 |
4 |
133/0.45 |
1.52 |
9.79 |
6 |
133/0.36 |
1.52 |
8.44 |
8 |
168/0.254 |
1.14 |
6.78 |
10 |
104/0.254 |
0.76 |
4.60 |
12 |
65/0.254 |
0.76 |
3.97 |
14 |
41/0.254 |
0.76 |
3.38 |
16 |
26/0.254 |
0.76 |
2.92 |
Note: The cables listed above have flexible structure.
Nominal cross sectional
area (AWG) |
Conductor structure
Number/diameter
of single wire |
Insulation thickness |
Maximum outer diameter |
14 |
7/0.62 |
0.76 |
3.38 |
12 |
7/0.77 |
0.76 |
3.83 |
10 |
7/0.98 |
0.76 |
4.46 |
8 |
7/1.23 |
1.14 |
5.97 |
6 |
7/1.56 |
1.53 |
7.71 |
4 |
7/1.96 |
1.53 |
8.74 |
2 |
7/2.47 |
1.53 |
10.45 |
1/0 |
19/1.89 |
2.03 |
13.46 |
2/0 |
19/2.12 |
2.03 |
14.86 |
4/0 |
19/2.68 |
2.03 |
17.26 |
350Kcmil |
37/2.47 |
2.41 |
22.34 |
500Kcmil |
37/2.95 |
2.41 |
25.47 |
750Kcmil |
61/2.82 |
2.79 |
30.96 |
Delivery
The cable shall be delivered in coil. Each package
of delivery shall be 100 meters, among which can
include the short wires of no less than 10 meters,
and the length of the short wires shall not be
over 10% of total length of each package.
Any delivery length shall be permitted in accordance
with the purchasers' requirement. |
|
|
|
|
|
|
|
|