Home Introduction Products Honor Client Productivity Experiment Contact Us
 
 
 
Products
 
    XLPE Insulated Power Cable of Rated Voltage up to and Including 35kV  
     
 
XLPE Insulated Power Cable of Rated Voltage up to and Including 35kV
  • Type and designation

Type

Designation

YJV

Copper conductor XLPE insulated PVC sheathed power cable

YJLV

Aluminum conductor XLPE insulated PVC sheathed power cable

YJY

Copper conductor XLPE insulated PE sheathed power cable

YJLY

Aluminum conductor XLPE insulated PE sheathed power cable

YJV22

Copper conductor XLPE insulated steel tape armored PVC sheathed power cable

YJLV22

Aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable

YJV23

Copper conductor XLPE insulated steel tape armored PE sheathed power cable

YJLV23

Aluminum conductor XLPE insulated steel tape armored PE sheathed power cable

  • Description of the purpose and usage properties

XLPE insulation means to change the linear structure of polyethylene molecule into three-dimension network structure by applying the physical or chemical cross-linking process. After cross-linking, the mechanical, thermo-aging and anti-environment stress properties of insulation material have been greatly improved, which makes the cable have excellent electrical and anti-chemical properties.

The cable listed is applicable for power distribution and transmission line of with rated voltage up to and including 35kV.

The maximum permitted long-term operating temperature of the cable shall be 90℃, with the maximum short-circuit (within 5 seconds) temperature being 250℃. The ambient temperature of installation of the cable shall not be less than 0℃.

The permitted bending radius of single core armored cable shall not be less than 20 times of the outer diameter of the cable, 15 times for multi-core armored cable, 15 times for single core non-armored cable, and 12 times for multi-core non-armored cable.

  • Standard

GB 12706,,IEC 60502,, or Enterprise standard

  • Production scope

Type

Cores number

Rated Voltage(kV)

3.6/6

6/10

8.7/15

12/20

26/35

Nominal cross-sectional area of conductor(mm²

YJV、YJLV、YJV22、YJLV22、YJV23、YJLV23、YJY 、YJLY

1

10~1000

16~1000

25~1000

35~1000

50~1000

3

10~400

16~400

25~400

35~400

50~400

Type

Cores number

Rated Voltage(kV)

0.6/1

1.8/3

Nominal cross-sectional area of conductor(mm²

YJV、YJY

1

1.5~1000

10~1000

YJLV、YJLY

2.5~1000

10~1000

YJV22、YJV23、YJLV22、YJLV23

10~1000

10~1000

YJV、YJY

2、3

1.5~400

10~400

YJLV、YJLY

2.5~400

10~400

YJV22、YJV23、YJLV22、YJLV23

4~400

10~400

YJV、YJY

3+1、3+2、4、4+1、5

1.5~400

10~400

YJLV、YJLY

4~400

10~400

YJV22、YJV23、YJLV22、YJLV23

4~400

10~400

Note: The optional flame-retardant or fire-resistant types of the cables listed are also available.

For single core power cable, aluminum tape or non-magnetic material instead of steel tape should be utilized for armoring.

  • Delivery

The delivery length of the cable shall not be less than 100 meters. The short end not less than 20 meters shall be permitted in delivery, and the length of short ends shall not be more than 10% of the total length of each delivery.

Any delivery length shall be permitted in accordance with the mutual agreement of the purchaser and the manufacturer.
 
     
 
 
  Copy right ©:Qingdao Cable Co., Ltd.
ADD:No.16#,Jifalongshan Road,Environmental Protection Industry Park,Jimo,Qingdao,266201 China
 
 
 