Type |
Designation |
Rated voltage (V) |
Standard |
227 IEC 01 (BV) |
Single-core rigid conductor non-sheathed cable for general purpose |
450/750 |
GB 5023 |
227 IEC 02 (RV) |
Single-core flexible conductor non-sheathed cable for general purpose |
450/750 |
GB 5023 |
227 IEC 05 (BV) |
Single-core solid conductor non-sheathed cable for internal wiring with conductor temperature of 70℃ |
300/500 |
GB 5023 |
227 IEC 06 (RV) |
Single-core flexible conductor non-sheathed cable for internal wiring with conductor temperature of 70℃ |
300/500 |
GB 5023 |
227 IEC 07 (BV-90) |
Single-core solid conductor non-sheathed cable for internal wiring with conductor temperature of 90℃ |
300/500 |
GB 5023 |
227 IEC 08 (RV-90) |
Single-core flexible conductor non-sheathed cable for internal wiring with conductor temperature of 90℃ |
300/500 |
GB 5023 |
227 IEC 10 (BVV) |
Light-duty PVC sheathed cable |
300/500 |
GB 5023 |
227 IEC 42 (RVB) |
non-sheathed parallel flexible cable |
300/300 |
GB 5023 |
227 IEC 43 (SVR) |
Flexible cable for indoor decorative illumination loops |
300/300 |
GB 5023 |
227 IEC 52 (RVV) |
Light-duty PVC sheathed flexible cable |
300/300 |
GB 5023 |
227 IEC 53 (RVV) |
Ordinary PVC sheathed flexible cable |
300/500 |
GB 5023 |
BV |
Copper conductor PVC insulated cable |
300/500 |
JB 8734 |
BLV |
Aluminum conductor PVC insulated cable |
450/750 |
JB 8734 |
BVR |
Copper conductor PVC insulated flexible cable |
450/750 |
JB 8734 |
BVV |
Copper conductor PVC insulated PVC sheathed round cable |
300/500 |
JB 8734 |
BLVV |
Aluminum conductor PVC insulated PVC sheathed round cable |
300/500 |
JB 8734 |
BVVB |
Copper conductor PVC insulated PVC sheathed parallel cable |
300/500 |
JB 8734 |
BLVVB |
Aluminum conductor PVC insulated PVC sheathed parallel cable |
300/500 |
JB 8734 |
RVS |
Copper conductor PVC insulated twisted flexible cable for connection |
300/300 |
JB 8734 |
AV |
Copper conductor PVC insulated wire for internal wiring of equipment |
300/300 |
JB 8734 |
AVR |
Copper conductor PVC insulated flexible wire for internal wiring of equipment |
300/300 |
JB 8734 |
AVRB |
Copper conductor PVC insulated parallel flexible wire for internal wiring of equipment |
300/300 |
JB 8734 |
AVRS |
Copper conductor PVC insulated twisted flexible wire for internal wiring of equipment |
300/300 |
JB 8734 |
AVVR |
Copper conductor PVC insulated and sheathed flexible cable for internal wiring of equipment |
300/300 |
JB 8734 |
AV-90 |
Copper conductor PVC insulated wire with temperature rating of 90℃ for internal wiring of equipment |
300/300 |
JB 8734 |
AVR-90 |
Copper conductor PVC insulated flexible wire with temperature rating of 90℃ for internal wiring of equipment |
300/300 |
JB 8734 |
AVP |
Copper conductor PVC insulated shielded wire for internal wiring of equipment |
300/300 |
JB 8734 |
RVP |
Copper conductor PVC insulated shielded flexible wire |
300/300 |
JB 8734 |
RVVP |
Copper conductor PVC insulated and sheathed shielded flexible wire |
300/300 |
JB 8734 |
RVP-90 |
Copper conductor PVC insulated shielded flexible wire with temperature rating of 90℃ |
300/300 |
JB 8734 |
AVP-90 |
Copper conductor PVC insulated shielded wire with temperature rating of 90℃ for internal wiring of equipment |
300/300 |
JB 8734 |
NLVV |
Aluminum conductor PVC insulated and sheathed direct-buried cable for rural area |
450/750 |
JB 2171 |
The product listed is applicable for power installations, fixed wiring and connection of electrical appliance of rated voltage up to and including 450/750V.
The maximum long-term permitted operating temperature of the cables with the type of 227 IEC 07 (BV-90)、227 IEC 08 (RV-90)、AV-90、AVR-90 or RVP-90 and AVP-90 shall be 90℃, and 70℃ for all the other types of cables. The ambient temperature of installation of the cable shall not be less than 0℃.
.Production scope
Note: The optional flame-retardant or fire-resistant types of the cables listed are also available.
The delivery length of the cable is 100 meters in coil, and at least 100 meters in reel. The short end of not less than 10 meters shall be permitted in delivery, and the length of short ends shall not be more than 10% of total length of each delivery.
Any delivery length shall be permitted in accordance with the mutual agreement of the purchaser and the manufacturer.