- Type and designation
Category |
Insulation |
Sheath |
Shield or armoring |
Characteristic |
Code |
Meaning |
Code |
Meaning |
Code |
Meaning |
Code |
Meaning |
Code |
Meaning |
K |
Control cable |
E |
Polyolefin |
E |
Polyolefin |
P |
Copper wire braid shield |
ZR |
Flame-retardant |
WD |
Low smoke non-halogen |
R |
Flexible cable for connection |
P2 |
Copper tape shield |
NH |
Fire-resistant |
无 |
Power cable |
YJE |
Cross-linked polyolefin |
YJE |
Cross-linked polyolefin |
22 |
Steel tape armoring |
R |
Flexible conductor construction |
Example:
KYJEE-WD-ZR means copper conductor cross-linked polyolefin insulated polyolefin sheathed low smoke non-halogen flame-retardant control cable.
RYJEEP-WD-ZR means copper conductor cross-linked polyolefin insulated polyolefin sheathed copper wire braid shielded low smoke non-halogen flame-retardant flexible cable for connection.
YJEE22-WD-NH means copper conductor cross-linked polyolefin insulated polyolefin sheathed steel tape armored low smoke non-halogen fire-resistant power cable.
- Description of the purpose and usage properties
The cable is used for power distribution, electrical connection, electrical instrument and signal transmittal and control of electronic apparatus in high rises, subway and other large public facilities.
The maximum permitted long-term operating temperature of the polyolefin insulated cable shall be 70℃, and 150℃ for cross-linked polyolefin insulated cable.
The permitted bending radius of the cable with copper tape shielding or steel tape armoring shall not be less than 12 times of the outer diameter of the cable, and 6 times for all the other types of cables.
Enterprise standard
Table 1Low smoke non-halogen control cable
Type |
Cores number |
Nominal cross-sectional area of conductor
(mm²) |
KYJEE-WD
KYJEEP-WD
KYJEEP2-WD |
2~10 |
0.75~10 |
12~14 |
0.75~6 |
16~61 |
0.75~2.5 |
KYJEE22-WD |
4~10 |
0.75~10 |
12~14 |
0.75~6 |
16~61 |
0.75~2.5 |
KYJEER-WD
KYJEERP-WD |
2~61 |
0.5~2.5 |
Table 2Low smoke non-halogen flexible cable for connection
Type |
Cores number |
Nominal cross-sectional area of conductor
(mm²) |
RYJE-WD |
1 |
0.5~300 |
RYJEE-WD
RYJEEP-WD |
2,3,4,5 |
0.75~6 |
Table 3Low smoke non-halogen power cable
Type |
Cores number |
Nominal cross-sectional area of conductor
(mm²) |
YJEE-WD |
1 |
1.5-800 |
2,3 |
4-300 |
4,3+1,3+2,4+1,5 |
4-240 |
YJEE22-WD |
1 |
4-800 |
2,3 |
4-300 |
4,3+1,3+2,4+1,5 |
4-240 |
Note: The optional flame-retardant or fire-resistant types of the cables listed are also available.
For single core power cable, aluminum tape or non-magnetic material instead of steel tape should be utilized for armoring.
Test item |
Test requirement |
Test result |
Test standard |
Oxygen index |
>28% |
48% |
ASTM D 2863 |
Burning Smoke Density of Cables |
Light transmittance ≥70% |
Pass |
GB12666.7 |
Causticity of burning flue gas |
PH≥4.3 |
Pass |
IEC754-2 |
Halogen gas content test |
HCL content≤50mg/m3 |
Pass |
IEC754-1 |
The delivery length of the cable shall not be less than 100 meters.
Any delivery length shall be permitted in accordance with the mutual agreement of the purchaser and the manufacturer. |